Is this radiant or baseboard? if it is radiant you don't want to go much higher than 140 on the mixer if you have hardwood floors and there should not be more than about 15 degrees drop over the run. I cant remember what the drop if for baseboard tho. if there is there may be another problem.
I have baseboard and hardwood floors. It is less than two years old. Is it normal to hear the water rushing through when it kicks on or does that mean that there is air in the system?
I have baseboard and hardwood floors. It is less than two years old. Is it normal to hear the water rushing through when it kicks on or does that mean that there is air in the system?
No its not normal. Sounds like you h ave air in the system that is restricting the flow. do you have bleeder valves on it?